Product Details
Technical Specifications
Type | IGTHP 0710/lP-XX |
---|---|
Standards | IEC 60364-7-710 |
Rated Power of Outgoing | 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA |
Power Supply Unit | Double Single Phase Lines |
Rated Voltage Line 1 - Line 2 | 230 Vac |
Rated Frequency | 50 I 60 Hz |
Rated Insulation Level | 3 kV / 1 min |
Input protection | gL Fuse |
Secondary Output Voltage | 230 Vac |
Output Protection | 2 Pole Fuses |
Monitoring | Isolation Resistance with LCD Display |
Alarm Output | Isolation Fault, Over Load, Switchover Failure, Over Temperature |
Functional Test | Advanced Isolation Fault and Switchover Test |
Leakage Current to Enclosure | <0.5mA |
Response Range | 50 - 500 kO |
Isolation Fault Detection Time | <1 s |
Switchover Time | <200 ms |
Operating Temperature | 5 ........ +50 °C |
Storage Temperature | 25 ...... +60 °C |
Panel Sizes | 405 X 405 X 1700 mm |
Distribution Outlet | 6 - 12 Outlets |
Cooling System | with Fan |
Protection Class | IP 31 |
Color | RAL 7035 / RAL 9003 |
Isolated Power Panels
Isolated power systems are used in group 2 rooms in
medical locations,
and they consist of auxiliary devices and test combinations such as
isolated power panels
and isolating transformer, isolation monitoring device, insulation fault
location devices '
remote alarm indicators.
The following medical locations that carrying vital importance in
hospitals and where
medical devices are directly connected to patients are defined as group
2 room in accordance
with I EC 60364-7-710 standard and isolated power systems are used in
these rooms.
The following rooms are of special concern
- Operating theatres
- Intensive care rooms
- Anesthetic rooms
- Premature baby rooms
- Operating preparation rooms
- Operating recovery rooms
- Heart catheterization rooms
- Angiographic examination rooms
- Power of system 3.15 / 4 / 5 / 6.3 / 8 / 10 kVA
- According to IEC 60364-7-710
- Monitoring insulation resistance, load current and temperature of the transformer
- Dimension of panel 405 x 405 x 1700 mm
- Color of panel RAL 7035 / RAL 9003
Thecnical Characteristics